Quantity
|
Out of stock
|
||
|
|
|||
|
|
|||
Motor for outdoor unit air conditioner YPY-35-6 L
Product description: The YPY-35-6 L motor is designed for use in outdoor units of air conditioners. It provides reliable fan rotation, which is critical for the effective operation of the cooling system and maintaining optimal indoor temperatures. This motor has a power rating of 35 W and operates at a voltage of 220-240 V with a frequency of 50 Hz.
Technical specifications
| Parameter | Value |
|---|---|
| Voltage | 220-240 V |
| Frequency | 50 Hz |
| Power | 35 W (0.35 A) |
| Rotation direction | Clockwise |
| Shaft diameter | 8 mm (with flat 8*7 mm) |
| Shaft length from dust cover to start of thread | 73 mm |
| Thread length of shaft | 11 mm |
| Thread diameter | 6 mm |
| Shaft length from dust cover to start of flat | 50 mm |
| Total length (motor and shaft) | 166 mm |
| Body height | 75 mm |
| Body diameter | 96 mm |
| Number of mounting holes | 4 pcs. Ø 5.5 mm (center-to-center=90 mm) |
| Connection | 3 terminals ("female") + 1 ground |
| Required capacitor | 2.5 µF, 450 V |
| Cable length | 0.9 m |
| Marking | YPY-35-6 |
How to choose the right product
When selecting a motor for an outdoor air conditioner unit, pay attention to the following characteristics:
- Voltage and frequency: Ensure that the motor specifications match your air conditioner's requirements.
- Shaft dimensions: Check the diameter and length of the shaft to avoid compatibility issues during installation.
- Capacitor: Make sure to use the correct capacitor that is compatible with the motor.
Possible causes of failure and prevention methods
The motor may fail for the following reasons:
- Overheating: This can occur due to insufficient ventilation or clogged filters. Regularly check and clean the filters.
- Bearing wear: Bearings may wear out over time. Use quality oil for lubrication and monitor the motor's condition.
- Voltage mismatch: Using incorrect voltage can lead to damage. Connect only to recommended power sources.
Difficulty of part replacement
Replacing the motor of an outdoor air conditioner unit is of medium difficulty. It is recommended to follow these steps:
- Disconnect the power to the air conditioner.
- Remove the cover of the outdoor unit.
- Disconnect the old motor and carefully remove it.
- Install the new motor, ensuring the correct rotation direction.
- Connect the capacitor and wires.
- Secure the motor and replace the cover.
- Turn the power back on and check the operation of the unit.
If you lack experience in air conditioner repairs, it is advisable to consult professionals for the replacement.